UNDERWRITERS LABORATORIES,
INC.
12 LABORATORY DR., P.O. BOX 13995, RESEARCH TRIANGLE PARK, NC
27709-3995
an independent, not-for-profit organization testing for public safety
File R12731
Project 89RT1476
June 23, 1989
REPORT
ON
FIRE RETARDANT COATINGS
CareChem Corp.
Hickory, NC
Copyright © 1989 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to reproduce this Report provided it is reproduced in its entirety.
Note: Test results below are for Flame-No-More™ products. They
are now
products and are the same product.
Thank you, Webmaster
DESCRIPTION
PRODUCT COVERED:
The products covered by this Report are fire retardant coatings.
USE:
The coatings covered in this Report are intended for use as interior coatings as permitted by the authorities having jurisdiction. The established Surface Burning Characteristics of the coatings are applicable only when the coating material is applied in the indicated number of coats, coverage rates, substrates, and overcoats and undercoats as specified in the published advices of Underwriters Laboratories Inc. and when the coating is maintained.
TEST RECORD NO. 1
EXAMINATION OF MATERIAL:
The materials used in this investigation were produced in a ready-to-use form under the observation of a representative of Underwriters Laboratories Inc. and were applied to the indicated test surfaces at the manufacturing location.
The compositions of the coating materials are of a proprietary nature and the formulas involved are on file at the Laboratories for use in the Follow-Up Service Program.
Various chemical and physical analyses were conducted on the coating materials and the results obtained from these analyses were employed in the establishment of specifications for use in the Follow-Up Service Program.
SURFACE BURNING CHARACTERISTICS TESTS:
SAMPLES
Substrate
Douglas Fir - The test decks were 21 in. wide and 8 ft long, composed of 1 by 4 in. tongue-and-groove Douglas fir flooring fastened together on the unexposed surface with wood furring strips. Three such decks were butted together end to end to form the 24 ft long test surface required to fill the Steiner Tunnel furnace.
Coatings
The coating materials were applied to the test surfaces by a representative of the submittor under the observation of a staff member of Underwriters Laboratories Inc. The coating materials were roll applied in one coat. The amount of coating applied was determined by weight.
Three coatings were evaluated under this investigation and the coatings have been identified as 1) "Flame-No-More Class A", 2) "Flame-No-More Class "B" Natural Finish" and 3) "Flame-No-More Class B Semi-Gloss Finish". The first coating was applied at a rate of 260 sq.ft./gal per coat; the second coating was applied at a rate of 150 sq.ft./gal per coat; and the third coating was applied at a rate of 150 sq.ft./gal.
The test samples were conditioned for 28 days at a temperature of 70 +/- 5°F and relative humidity of 45 to 55 percent before testing.
METHOD
The tests were conducted in accordance with the Standard of Underwriters Laboratories Inc., Tests for Surface Burning Characteristics of Building Materials, UL 723.
RESULTS
Data on flame spread and smoke developed appear in the following tabulations.
Flame Spread
The maximum distance the flame spreads along the length of the sample from the end of the igniting flame is determined by observation. The flame spread Classification of the material is derived by determining the area under the flame spread distance (ft) versus time (min) curve, ignoring any flame front recession, and using one of the calculation methods as described below:
1. If the total area (AT) is less than or equal to 97.5 min-ft (meter-minute x 3.3), the flame spread Classification is to be 0.515 times the total area (AT), FSC = 0.515 AT.
2. If the total area (AT) is greater than 97.5 min-ft (meter-minute x 3.3), the flame spread Classification is to be 4900 divided by 195 minus the total area (AT), FSC = 4900/ (195-AT).
| Test No. | Material | Calculated Value for Flame Spread |
|---|---|---|
| 1 | Blank Douglas Fir Decks | 102.5 |
| 2 | Blank Douglas Fir Decks | 122.9 |
| 1 | Flame-No-More Class A | 21.8 |
| 2 | Flame-No-More Class A | 22.8 |
| 3 | Flame-No-More Class A | 31.3 |
| 4 | Flame-No-More Class B Natural Finish | 39.0 |
| 5 | Flame-No-More Class B Natural Finish | 41.4 |
| 6 | Flame-No-More Class B Natural Finish | 36.6 |
| 7 | Flame-No-More Class B Semi-Gloss Finish | 24.6 |
| 8 | Flame-No-More Class B Semi-Gloss Finish | 29.3 |
| 9 | Flame-No-More Class B Semi-Gloss Finish | 31.9 |
Smoke Developed
The smoke developed during the test is indicated by the output of a photoelectric circuit operating across the furnace flue pipe. A curve is developed by plotting values of light absorption (decrease in cell output) against time. The calculated value for smoke developed Classification is derived by expressing the net area under the curve for the material under test as a percentage of the net area under the curve for untreated red oak.
| Test No. | Material | Calculated Value for Smoke Developed |
|---|---|---|
| 1 | Blank Douglas Fir Decks | 66.4 |
| 2 | Blank Douglas Fir Decks | 81.6 |
| 1 | Flame-No-More Class A | 313.5 |
| 2 | Flame-No-More Class A | 305.8 |
| 3 | Flame-No-More Class A | 307.7 |
| 4 | Flame-No-More Class B Natural Finish | 135.8 |
| 5 | Flame-No-More Class B Natural Finish | 127.5 |
| 6 | Flame-No-More Class B Natural Finish | 152.3 |
| 7 | Flame-No-More Class B Semi-Gloss Finish | 220.2 |
| 8 | Flame-No-More Class B Semi-Gloss Finish | 221.7 |
| 9 | Flame-No-More Class B Semi-Gloss Finish | 218.0 |
CONCLUSION
SURFACE BURNING CHARACTERISTICS:
The following Surface Burning Characteristics are established for the coatings evaluated under this investigation:
SURFACE BURNING CHARACTERISTICS:
| Douglas Fir Flame-No-More Class A |
Douglas Fir Flame-No-More Class B Natural Finish |
Douglas Fir Flame-No-More Class B Semi-Gloss Finish |
|
|---|---|---|---|
| Flame Spread | 25 | 40 | 30 |
| Smoke Developed | 300 | 140 | 200 |
FOLLOW-UP SERVICE PROGRAM:
The coatings covered by this Report will be placed under the Follow-Up Service of Underwriters Laboratories Inc.
The Classification Marking of Underwriters Laboratories Inc. attached to the product will be evidence that such a product has been produced under the Follow-Up Service Program. Such a Classification Marking will bear the information as shown below:
UNDERWRITERS LABORATORIES INC.
®
CLASSIFIED
FIRE RETARDANT COATINGS
SURFACE BURNING CHARACTERISTICS OF APPLIED COATINGS
| Douglas Fir Flame-No-More Class A |
Douglas Fir Flame-No-More Class B Natural Finish |
Douglas Fir Flame-No-More Class B Semi-Gloss Finish |
|
|---|---|---|---|
| Flame Spread | 25 | 40 | 30 |
| Smoke Developed | 300 | 140 | 200 |
| Number of preliminary coats | None | None | None |
| Rate per coat (sq ft per gal) | --- | --- | --- |
| Number of fire retardant coats | 1 | 1 | 1 |
| Rate per coat (sq ft per gal) | 260 | 150 | 150 |
| Number of overcoats | None | None | None |
| Rate per coat (sq ft per gal) | --- | --- | --- |
| Flash point of fire retardant coating: Closed cup, no flash |
| Report by: THOMAS PLENS Senior Engineering Assistant Fire Protection Department |
Reviewed by: DANIEL P. RYAN Engineering Group Leader Fire Protection Department |
TP/DPR:ajn
Carolina Fire-Safety.com
P.O. Box 107
Grover, NC 28073Please call or write for information.
Voice: (704) 937-3231
Fax: (704) 937-7795EMail: info@carolinafire-safetyNoSPAM.com
please remove the NOSPAM from above before sending, thanx
IMPORTANT!! Please put your phone number in any emails. Some Spam Blockers can keep you from receiving our emails.
Copyright 2007,2008, Carolina Fire-Safety.com
Flame-No-MoreTM and Flame-OutTM are registered trademarks of the CareChem Corporation (now Southern Polymer, Inc.).
Hosted by Maintained by www.hilton2000.com. Contact the webmaster with site related questions.
Modified last 08/03/2008 03:19 PM -0500 jh